AB7621 Modbus RTU Slave - CC Link Slave
- Supported Modbus RTU functions: 1, 2, 3, 4, 5, 6, 8, 15, 16, 22, 23
- Uses up to 4 occupied stations on CC-Link - configurable size
- Uses the CC-Link PLC profile for data exchange
- Modbus RTU transmission media RS485
- Support for CC-Link version 2.0 with extended data
Wysoka cena? Zaloguj się i kupuj taniej
Darmowa dostawa
Promocja cenowa na model HDR-15-5
Produkt przeznaczony wyłącznie do zastosowań profesjonalnychModele
-
Model Dostępność Gwarancja Schowek Twoja cenaTwoja cena Ilość produktów DodajAB7621Modbus RTU Slave - CC Link SlaveNa zamówienie Gwarancja: 3 980,00 zł4 895,40 złZaloguj się, aby poznać swoją cenę AB7621Modbus RTU Slave - CC Link SlaveDostępność: Na zamówienieCena netto:3 980,00 zł
Opis
The Anybus X-gateway copies I/O-data in both directions thus enabling data exchange between the two networks. Default I/O configuration is 20 bytes Input and 20 bytes Output. Changing default settings is very simple and is carried out using the RS232 configuration port and a standard terminal interface on a PC, such as Hyper Terminal for Windows.
The Modbus RTU Slave interface is implemented according to Modbus Protocol ref guide (PI-MBUS-300). All data is mapped to 3x and 4x Modbus areas meaning the Input Status and Output Register Word areas. The Modbus RTU standard baudrate is 19200 Bit/s but can be modified on the gateway between 1200 Bit/s to 57 600 Bit/s.
The CC-Link interface is a slave module for the CC-Link fieldbus system. It contains all the functionality needed to turn an application into a complete CC-Link remote device and it is configured to use the generic PLC profile. The CC-Link interface module is certified by the CLPA organisation and has proven conformance and interoperability with leading PLC´s, HMI´s etc
Specyfikacja
- Specyfikacja techniczna
| Size: | 126 mm x 110 mm x 42 mm |
| Power Supply: | 24 VDC (?10%) |
| Temperature: | 0-65°C |
| Current Consump: | max 300 mA |
| I/O Input: | Default 20 bytes, max 64 bytes (max 128 I/O-points and 16 words on CC-Link) |
| I/O Output: | Default 20 bytes, max 64 bytes (max 128 I/O-points and 16 words on CC-Link) |
| Mech Rating: | IP20/Nema1 |
| Config Method: | Windows Hyper Terminal |
| UL certification: | E203225, Listed 67AM, UL-1604 Class 1, Div 2, GP A, B, C, D, Temp Code T4 |
| ATEX certification: | ATEX 135419, II 3 G, EEx nL IIC T4, DEMKO 03 |
| Power supply connector: | 2-pole 5.08 mm Phoenix pluggable screw connector |
| Modbus RTU baudrate: | 1200 Bit/s to 57 600 Bit/s |
| Modbus RTU address: | Node address 1-247 |
| Modbus RTU connector: | D-sub 9-pin female |
| CC-Link baudrate: | 156kbps to 10Mbps |
| CC-Link address: | Station 1-64 |
| CC-Link connector: | 5-pole 5.08 mm Phoenix pluggable screw connector |
| CC-Link config.: | Configured by CC Link Master via CSP Config file (provided by HMS) |
| Price Group: | A |
| Order Code: | AB7621 |